DATE: October 25, 1995

TEST METHOD: ASTM D-1308: Standard Test Method for Effect of Household Chemicals on Clear and Pigmented Finishes. (Chemical soak test modified for evaluation with various concentrations of hydrogen peroxide immersion solutions. See Appendix for specific test procedure. Solutions were changed regularly to maintain concentration of H2O2.)

COATING SYSTEM: Plant applied PROTECTO 401 CERAMIC EPOXY internally lined ductile iron pipe (DIP) cut into 3 inch x 4 inch coupons.

TEST DURATION and CONDITIONS: 1080 hours (45 days), Room temperature, panels submerged 50% to provide liquid and vapor phase testing.

Coupons, cut from mill applied epoxy coated pipe, were subjected to specific 1080 hour (45 day), room temperature partial submersion in a series of concentrations of hydrogen peroxide H2O2).
The results are tabulated below.
 
CHEMICAL SYSTEM RESULTS
1 % H2O2 135/136 Pass: Coating unaffected, no undercutting or loss of adhesion; Some corrosion to back of coupon and from un protected hole drilled in top of coupon.
5% H2O2 126/131 Pass: Coating unaffected, no undercutting or loss of adhesion; Some corrosion to back of coupon and from unprotected hole drilled in top of coupon.
10% H2O2 123/125 Pass: Coating unaffected; Some corrosion to back of coupon and from un-protected hole drilled in top of coupon. Corrosion to metal at un-protected areas of coupon.
25% H2O2 121/122 Pass: Coating unaffected; Some corrosion to back of coupon from un-protected hole drilled in top of coupon. Corrosion to metal at un-protected areas of coupon.
50% H2O2 119/120 Pass: Coating unaffected; Some corrosion to back of coupon and from un-protected hole drilled in top of coupon. Corrosion to metal at un-protected areas of coupon.

CERTIFIED

_________________
Dr. George Mills
Date: 24 October 1995